Tongdy Control Technology Co., Ltd
|
Gold Index: 9977
Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Specifications
Gas detected | Carbon Dioxide (CO2) |
Sensing element | Non-Dispersive Infrared Detector (NDIR) |
Accuracy@25(77),2000ppm | ±40ppm + 3% of reading or ±75ppm (whichever is greater) |
Stability | <2% of FS over life of sensor (15 yr typical) |
Calibration interval | ABC Logic Self Calibration System |
Response time | <2 minutes for 90% step change |
Warm up time | 2 hours (first time) |
CO2 measuring range | 02,000ppm / 05,000ppm selectable in orders |
Sensor life | Up to 15 years |
Power supply | 24VAC/24VDC |
Consumption | 1.5 W max. ; 0.8 W avg. |
Analog outputs | 0~10VAC or 4~20mA selectable by jumpers |
Relay output | 1X2A switch load |
6 LED lights | 1st green light on as CO2 measurement≤600ppm |
Modbus interface | Modbus RS485 interface |
Operation conditions | 0~50(32~122); 0~95%RH, non condensing |
Storage conditions | 0~50(32~122) |
Net weight | 180g |
Dimensions | 100mm×80mm×28mm |
Installation standard | 65mm×65mm or 2”×4”wire box |
Approval | CE-Approval |
Features
1. Real-time detecting CO2 level.
2. NDIR infrared CO2 module inside with four CO2 detection range selectable.
3. CO2 sensor has Self-Calibration Algorithm and 15 years lifetime
4. Providing one analog output with voltage or current selectable
5. 0~10VDC/4~20mA selectable easily via jumpers
6. Special “L” series with 6 lights indicates CO2 level and makes CO2 level show clearly.
7. Provide a special model with a on/off relay output with a touch button to operate a fan control.
8. Design for HVAC, ventilation systems, offices, or other public places.
9. Modbus RS485 communication interface optional: 15KV antistatic protection, independent address setting
10. For duct probe CO2 transmitter, and CO2+ Temp.+ RH 3 in 1 transmitter, please see our other products.
Models Guide
Type | Model | Description |
CO2 Detector (1xanalog,1Xon/off output) | F2000TSM-CO2-S100-V/A-02 | 1Xanalog output, CO2 range: 0~2,000ppm |
F2000TSM-CO2-S100-V/A-05 | 1Xanalog output, CO2 range: 0~5,000ppm | |
F2000TSM-CO2-S100-V/A-20 | 1Xanalog output, CO2 range: 0~20,000ppm | |
F2000TSM-CO2-S100-V/A-50 | 1Xanalog output, CO2 range: 0~50,000ppm | |
F2000TSM-CO2-S110-V-02 | 1X0~10V output and 1xon/off output CO2 range: 0~2000ppm | |
CO2 Detector (1xanalog output, Modbus RS485 interface) | F2000TSM-CO2-S101-V/A-02 | 1Xanalog output, Modbus RS485 communication. |
F2000TSM-CO2-S101-V/A- 05 | 1Xanalog output, Modbus RS485 communication | |
F2000TSM-CO2-S101-V/A-20 | 1Xanalog output, Modbus RS485 communication. | |
F2000TSM-CO2-S101-V/A-50 | 1Xanalog output, Modbus RS485 communication. | |
CO2 Detector With 6 indicator lights | F2000TSM-CO2-L101-N-02/05 | 6 lights indicate CO2 measurements range, |
F2000TSM-CO2-L100–V/A-02/05 | 6 lights indicate CO2 measurements range, | |
F2000TSM-CO2-L101–V/A-02/05 | 6 lights indicate CO2 measurements range,1x analog output, Modbus RS485 interface | |
F2000TSM-CO2-L110-V-02 | CO2 transmitter and indication, 1x 0~10VDC output, 1X on/off output with a touch button. CO2 range: 0~2000ppm | |
F2000TSM-CO2-L110-N-02 | 6 lights indicate CO2 measurements range, | |
F2000TSM-CO2-L111-N-02 | 6 lights indicate CO2 measurements range, |
Wiring Diagram
Mounting & Dimension
Tongdy Control Technology Co., Ltd [China (Mainland)]
Business Type:Manufacturer
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)