Tongdy Control Technology Co., Ltd
|
Gold Index: 9977
Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Specifications
Gas detected |
Carbon Dioxide (CO2) |
Sensing element |
Non-Depressive Infrared Detector (NDIR) |
CO2 NDIR life |
>10 years |
CO2 range |
0~5000ppm |
Accuracy@25(77) |
±40ppm + 3% of reading (0~5,000ppm) |
Stability |
<2% of FS over life of sensor (15 yr typical) |
Calibration interval |
ABC Logic Self Calibration Algorithm |
CO2 setting & Display resolution |
1ppm |
Pressure Dependence |
Can be preset the altitude by the end users to eliminate the pressure influence via a inside software |
Temperature& RH sensor (optional) |
Combined digital temperature and relative humidity sensor |
Temperature measurement range |
060(32140) |
Humidity measurement range |
0~100%RH |
Temperature& RH accuracy |
±0.5 / ±3%RH |
Option: 1X dry contact output |
Rated currency for contact point: 2A 220VAC/30VDC, resistance load |
Operation condition |
060, 095%RH (non-condensing) |
Power supply |
24VAC/VDC ±10% wiring connection |
Consumption |
3.5W/ Max, 2.5W/ Average |
Weight |
380g |
Dimensions |
130mm×90mm×40mm |
Connections Interface |
Locate in interface of connection |
Installment standard |
65mm×65mm or 2”×4” wire box |
Wiring standard |
Wire section area<1.5mm2 |
Approval Standard |
CE-Approval |
Presetting and operation |
Buttons and internal DIP switches |
Sampling alternation |
Preset the sampling alternation during 60s to 1h. The general maximum |
Software Features |
Outputs date is in .txt format |
Description
1. Real-time monitoring carbon dioxide (CO2) measurements during 0ppm to 5,000ppm range
2. Optional real-time monitoring temperature from -20 to 60 and relative humidity from 0 to 100%RH
3. Non-dispersive infrared (NDIR) CO2 sensor with self-calibration, 15 years lifetime
4. The 3-LED indicator lights indicate three CO2 measured ranges
5. LED lights brightness adjustable
6. Easy preset CO2 level for buzzer alert (optional)
7. Provide 1X On/Off dry contact output to control alternative a ventilator and a CO2 generator
8. An internal data logger is used to record CO2 measurements as well as optional temperature and RH% measurements.
9. With super large capability memorizer, it can save data of up to 115 days
10. Provide the software to preset the sampling time, read and record CO2/temperature&RH levels on PC
11. Post the data from the internal memorizer by any USB disk, and copy the data to a PC
Applications
The memorial CO2 monitor/controller not only very easily to be used as a CO2 monitor and controller, but also as a recorder of the measurements. Application in schools, kindergartens, office buildings, greenhouses and so on.
Buttons/LCD/USB Connection
Mounting and Dimensions
Models Guide
item |
model |
description |
1 |
F2000IAQ-CO2-3100U |
CO2 Detector&Monitor with LCD display, 3 LED lights indicates CO2 levels range. Data logger records CO2 measurements with a USB disk to move the data to a PC. |
2 |
F2000IAQ-CO2-3101U |
CO2 Monitor&Controller with LCD display, 3 LED lights indicates CO2 levels range. 1X relay On/Off control output. |
3 |
Option -TH (postfi (for above items) |
Temperature and RH monitoring and data recordering option for above items. |
Wiring Diagram
Tongdy Control Technology Co., Ltd [China (Mainland)]
Business Type:Manufacturer
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)