Tongdy Control Technology Co., Ltd
|
Gold Index: 9977
Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Specifications
Monitoring parameters | CO2 | Air Quality (VOC) | Temperature | Relative humidity |
Sensing element | Non-Dispersive Infrared Detector (NDIR) | Semiconductor mix gases sensor | Digital combined temperature and humidity sensor | |
Measuring range | 0~2000ppm(default) | 0~30ppm | 0~50(32~122) (default) | 0~100%RH |
Display Resolution | 1ppm | 5ppm | 0.1 | 0.1%RH |
Accuracy@25(77) | ±50ppm + 3% of reading | ------- | ±0.4 (0~50) | ±3%RH (20%-80%RH) |
Life time | 15 years (normal) | 57 years | 10 years | |
Calibration cycle | ABC Logic Self | ------- | --------- | -------- |
Response Time | <2 minutes for 90% change | <1 minute | <10 seconds to reach 63% | |
Warm up time | 2 hours (first time) |
Electrical Characteristics | ||
Power supply | 24VAC/VDC |
|
Consumption | 3.5 W max. ; 2.5 W avg. |
|
Analog Outputs | Two or three analog outputs |
|
Modbus RS485 interface | RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address |
|
Conditions of Using and Installation | |
Operation conditions | 0~50(32~122); 0~95%RH, non condensing |
Storage conditions | 0~50(32~122)/ 5~95%RH |
Weight | 320g |
Installation | Fixed on the air duct with 100mm installation hole size |
IP class of the housing | PC/ABS |
Standard | CE-Approval |
Application
Residential houses, exhibition halls, restaurants, shopping malls, sports gymnasiums, conference rooms, etc.
Museums, theaters, offices, classrooms, train stataions, airports, etc.
Dimensions and Mounting
Models Guide
TG9- X 1 8 2 L – Y 02/05 E –Tab
X: analog output
3- 3Xanalog outputs for CO2 + Air Quality (VOC) + Temp. /RH (selectable by jumpers)
2- 2xanalog outputs for CO2 + Air Quality (VOC)
0- no analog output
1: Modbus interface (with outputs for real-time measurement of CO2+ Air Quality (VOC) +Temp. +RH)
8: CO2 sensor code
2: Air Quality (VOC) sensor code
L: LCD display
No L indicates no LCD
Y: Analog output type
A- 4~20mA (selectable via jumpers)
V- 0~10VDC (default)
V5- 0~5VDC (NOTE: If 0~5VDC is chosen, then options of 0~10VDC or 4~20mA will not be available
02/05: CO2 measurement range
02- 0~2000ppm (default)
05- 0~5000ppm
E: extended duct probe up to 209mm
No E indicates the standard probe length of 139mm
Tab: temperature scaling
T05: 0~50(32~122) default
T06: 0~60(32~140)
Without the item option indicates no output for temperature measurement.