Tongdy Control Technology Co., Ltd
|
Gold Index: 9977
Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Specifications
Gas detected |
Ozone |
Sensing element |
Semiconductor ozone gas sensor |
Power Supply |
24VAC/VDC±10% |
Consumption |
2.2 W |
Temperature sensor |
NTC |
Warm up time |
96 hours (first time) 1 hour(operation) |
Signal Update |
2s |
O3 Measuring Range |
10~500ppb |
O3 measuring precision |
±15ppb + 20% reading (15~35/30~60%RH) |
Six indicator lights |
The first green indicator light:O3≤49ppb The first and the second green indicator lights:50ppb~99ppb The first yellow indicator light:100ppb~199ppb The first and the second yellow indicator lights:200ppb~299ppb The first red indicator light:300ppb~399ppb The first and the second indicator lights:O3 ≥400ppb |
Modbus interface |
Modbus RS485 protocol with19200bps(default), 15KV antistatic protection, independent base address, 31 max network nodes |
Relay output(optional) |
One dry contact output, rated switching current 2A(resistance load). Provide four ozone ranges to be selected to control the relay turn-on/turn-off (50ppb /100ppb-default / 200ppb/ 300ppb) |
Analog output(optional) |
1X0~10VDC or 4~20mA for ozone measurements |
Operation temperature |
550 (41122) |
Operation humidity |
080%RH,non condensing |
Weight |
190g |
Dimensions |
100mm×80mm×28mm |
Installation standard |
65mm×65mm or 2”×4” wire box |
Housing/ IP rate |
PC/ABS plastic fireproof material, IP30 |
Standard |
CE-Approval EN60730-1:2000 +A1:2004 + A16:2007 + A2:2008 Directive: 2004/108/EC |
Features
Real time detect and indicate indoor ozone level
Design temperature compensation for ozone measurements
Featured 6 LED lights indicates different ozone levels
Five years lifetime
Optional 1x dry contact output to control an O3 generator or 1xanalog output for ozone measurements
Modbus RS485 interface
Easy zero calibration
Higher performance with lower price
Applications
1. Specially used for detecting indoor ambiance quality
2. Real time measuring ozone level and analyzing: alarm when ozone level is over proof, control ozone concentrations by controlling related devices in order to reach a certain level in some special places
3. Anti-epidemic and disease prevention, sanitary inspection, environment protection, health protection, etc.
Dimensions and Mounting
Models Guide
ITEM |
MODEL |
DESCRIPTION |
Ozone Detector/Controller |
F2000TSM-O3-L100C |
Ozone indicator with 6 LED indicator lights Modbus RS485 interface |
F2000TSM-O3-L101C |
Ozone indicator with 6 LED indicator lights One dry contact output, Modbus RS485 interface |
|
F2000TSM-O3-L110C |
Ozone indicator with 6 LED indicator lights One analog output, Modbus RS485 interface |
Wiring Diagram
Tongdy Control Technology Co., Ltd [China (Mainland)]
Business Type:Manufacturer
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)