Model No.: AIA-1

Specifications
 
<table border="1" cellpadding="0" cellspacing="0" style="

Specifications

 

Monitoring parameters

CO2

TVOC

Temperature

Relative humidity

Sensing element

Non-Dispersive Infrared Detector (NDIR)

Semiconductor mix gases sensor

Digital combined temperature and humidity sensor

Measuring range

0~5000ppm

1~30ppm

-20~60

0~100%RH

Display Resolution

1ppm

5ppm

0.1

0.1%RH

Accuracy@25(77)

±60ppm + 3% of reading

±10%

±0.5

±4.5%RH

Life time

15 years (normal)

57 years

10 years

Stability

<2%

——

<0.04

per year

<0.5%RH

per year

Calibration cycle

ABC Logic Self

Calibration

        ——

——

——

Response Time

<2 minutes for 90% change

<1 minute

(for 10ppm hydrogen,

30ppm ethanol)

<5 minute

(for a cigarette)

in 20m2 room

<10 seconds to reach 63%

Warm up time

72 hours (first time)

1 hour (operation)

 

Electrical Characteristics

Power supply

100~240VAC

18~24VAC/VDC with the power adaptor available

Consumption

3.5 W max. ; 2.5 W avg.

 

Display and Alarm

LCD Display

Green: CO2<1000ppm (optimal air quality)

TVOC: or  (low pollution)

 

Yellow: CO2>1000ppm (moderate air quality)

     TVOC: or  (medium pollution)

 

Red:   CO2>1400ppm (poor air quality)

   TVOC: or (heavy pollution)

 

Two modes selectable: both CO2 and TVOC over the above setpoints(default)

Either CO2 or TVOC over the above setpoint

 

Conditions of Using and Installation

Operation conditions

-10~50(14~122); 0~95%RH, non condensing

Storage conditions

0~50(32~122)/ 5~90%RH

Weight

200g

Dimensions

130mm(L)×85mm(W)×36.5mm(H)

Installation

Desktop or wall mount (65mm×65mm or 85mmX85mm or 2”×4” wire box)

Housing IP class

PC/ABS, protection class: IP30

 

 

Features 

 

1. NDIR infrared CO2 sensor with special Self Calibration makes the CO2 measurement more accurate     and more reliable.

2. More than 10 years lifetime of CO2 sensor

3. More than 5 years lifetime of Semi-conductor TVOC (mix gases) sensor

4. Digital compositive temperature and humidity sensor with more than 10 years lifetime

5. Three-color (green/yellow/red) LCD backlit indicating optimal/moderate/poor ventilation

6. Two alarm ways: buzzer alarm and backlight colours switch

7. Provide optional 1xrelay output to control a ventilator

8. The touch button for easy operationExcellent performance for IAQ detection and monitoring in home and office.

9. 220VAC or 24VAC/VDC power selectable; power adaptor available; desktop and wall mounting type available 

   

Application

 

a. Hotel, exhibition hall, hospital, shop, restaurant, air port, train station, theater and other public places

b. House, villa, office, meeting room, classroom and other rooms

c. All ventilation systems 

 

Mounting, Dimensions and Wiring

 

 

Models Guide

 

Model

Name

Description

Power Supply

G01-CO2-B530C

bigPhoto
 Mr. Tian Qing

Tel: 86-10-59738930
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Tongdy Control Technology Co., Ltd [China (Mainland)]


Business Type:Manufacturer
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)

You May Like:

Product (195)