Specificcations
General Data | |
Power supply | G03-PM10-300P: 5VDC with a power adaptor |
Work consumption | 1.2W |
Warm-up time | 60s (first using or using again after a long-time power off) |
Monitor parameters | PM10, air temperature, air relative humidity |
LCD display | LCD six backlit, displays six levels of PM10 concentrations and one hour |
Installation | Desktop-G03-PM10-300P |
Storage condition | 0~60/ 5~95%RH |
Dimensions | 85mm×130mm×36.5mm |
Housing materials | PC+ABS materials |
Net weight | 198g |
IP class | IP30 |
Temperature and Humidity Parameters | |
Temperature humidity sensor | Built-in high precision digital integrated temperature humidity sensor |
Temperature measuring range | -20~50 |
Relativehumidity measuring range | 0~100%RH |
Display resolution | Temperature:0.01 Humidity:0.01%RH |
Accuracy | Temperature:<±0.5@30 Humidity:<±3.0%RH (20%~80%RH) |
Stability | Temperature:<0.04 per year Humidity:<0.5%RH per year |
PM10 Parameters | |
Built-in sensor | Dust particle sensor |
Sensor Type | Optical sensing with an IR LED and a photo-sensor |
Measuring range | 0~800μgm3 |
Display resolution | 0.1μgm3 |
Measuring accuracy(1h average) | ±15µg+10% of reading @ 20~35,20%~80%RH |
Working life | >5 years (avoid to close lampblack, dust, great light) |
Stability | <10% measurement decline in five years |
Option | |
RS485 interface | MODBUS protocol,19200bps, 15KV antistatic protection |
Models
Features
LCD backlit indicate PM10 concentration
Air Quality Levels | PM10 24h Average Concentration | Effects on Health | ||
LCD Color | PM10 | Air Type | μg/m3 |
|
Green | Level I | Very good | 0-50 | Good air quality, almost no air pollution |
Yellow | Level II | Good | 51-150 | Acceptable air quality, but some pollutants may has a weak effect on health of a handful of high sensitive people. |
Orange | Level III | Light pollution | 151-250 | The symptom of susceptible people are mild sharpened and healthy people come on an symptom of irritation. |
Red | Level IV | medium pollution | 251-350 | Further aggravate symptoms of vulnerable groups, it may has an impact on healthy people heart, lungs and respiratory system. |
Purple | Level V | heavy pollution | 351-420 | Symptoms of vulnerable groups are further aggravated. Healthy people generally appear symptoms |
· Red-brown | Level VI | Serious pollution | >421 | The exercise tolerance of healthy people is reduced with noticeable symptoms, and some symptoms appear ahead of time. |